Unlike an initial motor purchase where your decision is limited to procuring a standard versus a premium efficiency motor, a motor failure or burnout produces three alternatives. Your options are to rewind the failed motor, purchase a new standard-efficiency motor, or purchase an energy-efficient replacement motor.
For this scenario, motor installation labor costs are again not included as the existing motor must be removed and reinstalled anyway.
Assuming that the failed motor can be rewound, the baseline or lowest initial cost approach is to rewind the motor to its original specifications. As some older U-Frame motors were built with oversized slots, it is sometimes possible to perform a “high-efficiency” rewind and slightly increase the efficiency of the motor by adding more copper to reduce I2R losses.
If the original unit was wound with aluminum wire, it should be replaced with copper.
A motor should be rewound with the same (or larger) winding wire size and configuration. If a repair shop does not have the correct wire size in stock and uses a smaller diameter wire, stator I2R losses will increase.
While a decrease in the number of turns in a stator winding reduces the winding resistance, it also shifts the point at which the motor’s peak efficiency occurs toward higher loads and increases the motor’s mag-netic field, starting current, locked rotor, and maximum torque. A change from 10 to 9 turns will increase the starting current by 23 percent, which can cause problems in the electrical distribution and motor protection systems.
In a typical rewind, the stator is heated to a temperature high enough to bum out its winding insulation. The windings are then removed and replaced.
For both standard and high-efficiency motors, the rewind shop should follow the motor manufacturers’ rec-ommended burnout temperature specifications.
When stripping out the old windings, it is essential to keep the stator core below 700°F. If the stator core gets too hot, the insulation between the stator laminations will break down, increasing eddy current losses and lowering the motor’s operating efficiency.
After being damaged, the lamination insulation cannot be repaired nor the efficiency loss restored without under going a major repair such as restacking the iron. The motor also becomes less reliable. Insulation removal techniques vary between rewind shops and should be investigated prior to deciding where to have the motor rewound.
Some shops have core loss testers and can screen motors determine if they are repairable prior to stripping. The repair shop should also determine and eliminate the cause for a motor’s failure.
Aside from proper strip-ping procedures, the motor owner should ensure that the rewind shop does the following:
- Uses proper methods of cleaning
- Installs Class F or better insulation
- Uses phase insulation between all phase junctions
- Uses tie and blocking methods to ensure mechani-cal stability
- Brazes rather than crimps connections
- Uses proper lead wire and connection lugs
- Applies a proper varnish treatment
As motor design characteristics (such as slot geometry and configuration), failure modes, rewind practices, and materials specifications and treatments vary, it is impossible to identify a “typical” rewind cost for a motor with a given horsepower, speed, and enclosure.
Motor efficiency losses after rewinds also vary considerably. While dynamometer tests conducted by the Electrical Apparatus Service Association indicate that new motors, when properly stripped and rewound, can be restored to their original efficiency, field tests on motors from a variety of manufacturing plants indicate that losses are typically higher in motors that have been rewound-perhaps because of thermal shock suffered during the motor failure.
An analysis of core loss tests taken over a 1 year period in General Electric repair facilities indicates that average core losses are 32 percent higher than normal for motors that had been previously rewound. General Electric also conducted a test of 27 rewound motors in the 3- to 150-hp size range.
The test indicates that total losses increased by 18 percent for motors that have been rewound compared to those that have not been rewound.
Rewound motors can exhibit severe efficiency losses, especially if they were rewound more than 15 years ago or have been rewound several times. Rewind losses of 5 percent or more are possible.
When should a energy-efficient motor be purchased in lieu of rewinding a failed standard-efficiency motor?
This decision is quite complicated as it depends on such variables as the rewind cost, expected rewind loss, energy-efficient motor purchase price, motor horse-power and efficiency, load factor, annual operating hours, electricity price, and simple payback criteria.
At least some of the time, rewinding will be the best decision. The prospects for a good rewind are greatly im-proved if you keep good records on your motors and provide them to the repair shop. Repair shops often can’t get complete specifications from manufacturers. Read More